7 Product-specific CAN objects XN300 slice modules
7.24 XN-322-1DCD-B35
314
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.24.1 Write PWM Sequenz Data (Object 0x20E0 to 0x20E3)
The four objects 0x20E0 to 0x20E3 are used to transmit the PWM output
sequence for motor control to the XN300 module.
Design of the data bytes:
0x40E3
UNSIGNED8
PDLED1
PWM Period Duration Register LED1
–
ro
SDO
0x40E4
UNSIGNED8
PDLED2
PWM Period Duration Register LED2
–
ro
SDO
0x40E5
UNSIGNED32
DCMotorI2TLimit
DC Motor I2T Value Limit
–
rw
SDO
Index
(hex)
Data Type
Name
Function
Mapping
Access
ACHTUNG NOTICE
Select period duration t
p
in line with the output sequence:
t
p
= t
OutputSequence =
t
OutputSeq... +
t
OutputSequence4
Failure to do so may result in undesired XN300 slice module
states.
Feature
Description / Value
EDS
Name
WRSeq1
Object 0x20E0
[MxSubExt20Ex]
ParameterName=WRSeq1
ObjectType=0x7
DataType=0x0006
AccessType=wo
PDOMapping=1
Count=1
WRSeq2
Object 0x20E1
WRSeq3
Object 0x20E2
WRSeq4
Object 0x20E3
Description
Write PWM Sequence Data
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
wo
Default value
0000
hex
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
Motor rotation
TC
Time value for determining the pulse width t
OutputSequence n
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...