7 Product-specific CAN objects XN300 slice modules
7.15 XN-322-7AI-U2PT
196
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.15.13 Channel Measuring Configuration (Object 0x5080)
Object 0x5080 can be used to configure the measuring method for a chan-
nel.
Data word structure:
Word 0:
Feature
Description / Value
EDS
Name
ChannelMeasuringConfig
[MxSubExt5080
ParameterName=ChannelMeasuringConfig
ObjectType=0x7
DataType=0x0006
AccessType=rw
DefaultValue=1
PDOMapping=0
Count=1
Description
Channel Measuring Configuration
Object Code
ARRAY
Mapping
SDO
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
rw
Default value
0000
hex
Word
Sub index
1
≦
n
≦
254
B1
5
B1
4
B1
3
B1
2
B1
1
B1
0
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Data bit
Designation
Description
Notes
0
Analog Input 1
0 = Analog measurement ± 10V
1 = Temperature measurement
1
0 = KTY10 Sensor
1 = PT1000 Sensor
2
0 = Differential measurement
1 = AI1- grounded measurement
3
Analog Input 2
0 = Differential measurement
1 = AI1- grounded measurement
4
Analog Input 3
0 = Differential measurement
1 = AI1- grounded measurement
5
Analog Input 4
0 = Differential measurement
1 = AI1- grounded measurement
6
Analog Input 5
0 = Differential measurement
1 = AI1- grounded measurement
7
Analog Input 6
0 = Differential measurement
1 = AI1- grounded measurement
8
Sensor selection
0: KTY10 Sensor
1: Pt1000 Sensor
9-15
reserved
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...