7 Product-specific CAN objects XN300 slice modules
7.18 XN-322-8AO-U2
230
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
Manufacturer-specific objects
Index range for the XN-322-8AO-U2 module: x0D0 to x0DF
7.18.1 Write Analog Output 16-Bit (Object 0x6411)
Object 0x6411 transmits the digital value of the channels' analog signal out-
puts. The object's data is automatically entered into the receive PDOs
(default mapping).
Index
(hex)
Data Type
Name
Function
Mapping
Access
0x1027
UNSIGNED16
ModuleID
Module Identification Number
Identification Number (Object
0x1027)”, page 76
–
ro
SDO
0x20D0
INTEGER16
OutputChannel1
Output Channel 1
Manual
rw
PDO
0x20D1
INTEGER16
OutputChannel2
Output Channel 2
Manual
rw
PDO
0x20D2
INTEGER16
OutputChannel3
Output Channel 3
Manual
rw
PDO
0x20D3
INTEGER16
OutputChannel4
Output Channel 4
Manual
rw
PDO
0x20D4
INTEGER16
OutputChannel5
Output Channel 5
Manual
rw
PDO
0x20D5
INTEGER16
OutputChannel6
Output Channel 6
Manual
rw
PDO
0x20D6
INTEGER16
OutputChannel7
Output Channel 7
Manual
rw
PDO
0x20D7
INTEGER16
OutputChannel8
Output Channel 8
Manual
rw
PDO
0x30D0
UNSIGNED16
ModuleDiag
Module Diagnostic Messages
Manual
ro
PDO
0x4001
VISIBLE STRING
SerialNumber
“6.2.8 Serial Number (Object
0x4001)”, page 78
–
const
SDO
0x4004
UNSIGNED8
UserLEDControl
“6.2.11 User LED Control
(Object 0x4004)”, page 81
–
rw
SDO
0x400C
VISIBLE STRING
ProductName
Product Name
Name (Object 0x400C)”, page
82
–
ro
SDO
0x40D0
UNSIGNED16
FirmwareVersion
Firmware Version
–
ro
SDO
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...