3 Commissioning
3.1 Take system bus into operation
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
41
▶
Make sure that all the I/O slice modules in the target configuration are
actually present on the system bus.
Storing the target configuration in the gateway's device memory
The target configuration needs to be imported the first time the device is
commissioned, whenever a module is replaced, and whenever the module
layout on the system bus changes.
Requirements that must be met in order to import the target configuration:
•
All slice modules must be locked in place together with the gateway in
the form of a system block and must be connected to the system bus.
•
Voltage POW is applied to the gateway and the POW LED lights up.
•
The planned power supply modules must be connected.
•
The status LEDs on the I/O slice modules must be on or must be flash-
ing.
To import the target configuration, follow the steps below:
▶
Set DIP switch 9 to the "OFF" position.
▶
Switch on the device's power supply.
The gateway will determine which I/O slice modules are currently on the sys-
tem bus and will store that configuration as the target configuration in its
device memory. The I/O LED will flash green to indicate that the device is
running without a config check.
▶
Set DIP switch 9 to the "ON" position.
▶
In order for the switch position change to be applied, switch the device's
power supply off and then back on.
When the device is switched on, the workflow in
be followed. The green I/O led will show a continuous light to indicate that
the device is running with the config check function on.
If DIP switch 9 is switched to the OFF position during operation, it will be
necessary to switch the device's power supply off and then back on.
→
The position of DIP switch 9 will be read only when the device is
powered on.
→
If the I/O LED shows a continuous red light, this means that no
addresses have been assigned to any of the XN300 modules.
Check the system bus and check the system block to make
sure that all I/O slice modules are properly locked in place with
each other.
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...