8 Station variants
8.5 Loading new firmware onto the gateway
Gateway XN-312-GW-CAN 06/16 MN050003-DE
www.eaton.eu
365
Once the transfer is successfully completed, you will get a corresponding
message. The GW LED will show a solid green light.
▶
Now switch the gateway off, change the node ID to the value you want
(1–31), and switch the gateway back on.
The gateway will start running with the new firmware.
For running the gateway in "station variants" mode
▶
Set the node ID for the gateway, e.g., to <2>.
▶
Check that the node ID has been entered in XSOFT-CODESYS Register
...
▶
Power cycle the gateway by turning it off and then back on.
▶
Select the gateway in the PLC configuration and, in the "General" tab,
enable the "Autoconfig. PDO Mapping" option. This will enable default
mapping.
Setting a fixed baud rate
To turn off automatic baud rate detection and set a fixed baud rate instead,
follow the steps below:
▶
Use DIP switches 6–8 to set the baud rate you want on the gateway,
e.g., 125 kHz.
▶
In XSOFT-CODESYS, select the gateway and, in the "Baud rate" field in
the "PLC settings" tab, select the same baud rate you just set, e.g., 125
kHz.
→
TIP: A gateway without baud rate autodetection will result in
faster initialization, as automatic baud rate detection will be dis-
abled.