7 Product-specific CAN objects XN300 slice modules
7.18 XN-322-8AO-U2
232
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
Design of the data bytes:
7.18.3 Module Diagnostic Messages (Object 0x30D0)
Object 0x30D0 contains status information on the module's general operat-
ing status.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Byte 1:
Sub-Index 1
≦
n
≦
254
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Feature
Description / Value
EDS
Name
ModuleDiag
[MxSubExt30D0]
ParameterName=ModuleDiag
ObjectType=0x7
DataType=0x0006
AccessType=ro
PDOMapping=1
Count=1
Description
Module Diagnostic Messages
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
ro
7
6
5
4
3
2
1
0
–
–
–
Data bit
Description
0
reserved
1
0 = sync OK
1 = no sync
2
0 = OK
1 = FLASH Data CRC Error
3
0 = OK
1 =RAM Data CRC Error
4
0 = OK
1 = Inconsistent FLASH Data
5 – 7
reserved
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...