7 Product-specific CAN objects XN300 slice modules
7.9 XN-322-12DO-P17
138
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.9.3 InputVoltageState(Object 0x3040)
Object 0x3040 contains information on the module's power supply.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Feature
Description / Value
EDS
Name
InputVoltageState
[MxSubExt3040]
ParameterName=InputVoltageState
ObjectType=0x7
DataType=0x0005
AccessType=ro
PDOMapping=1
Count=1
Description
Input Voltage State
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
ro
Default value
00
hex
Data bit
Designation
Meaning
Notes
0
Power supply, outputs 1–
4:
0 = No power
1 = Power OK (24 V)
1
Power supply, outputs 5–
8:
0 = No power
1 = Power OK (24 V)
2
Power supply, outputs 9–
12:
0 = No power
1 = Power OK (24 V)
3-7
reserved