7 Product-specific CAN objects XN300 slice modules
7.16 XN-322-8AI-I
202
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
Default value
•
FALSE (0)
Object 0x6401 is not enabled and cannot transmit any analog input val-
ues.
•
TRUE (1)
Object 0x6401 is enabled and can transmit analog input values.
7.16.4 Analog Input Interrupt Upper Limit Integer (Object 0x6424)
Object 0x6424 defines an upper limit and affects the transmission of object
0x6401 accordingly
Object 0x6401 will be transmitted (CAN transmission) if all of the following
conditions are met:
•
The analog input value (ENTRY into 0x6401) is equal to or greater than
the upper limit (Upper Limit 0x6424).
•
Object 0x6421 is set to enable.
•
The global interrupt in object 0x6423 has been enabled with: TRUE.
Design of the data bytes:
Feature
Description / Value
EDS
Name
Analog Input Global Interrupt Enable
[MxFixed6423]
ParameterName=AnalogInputGlobalInterruptEnable
ObjectType=0x7
DataType=0x0001
AccessType=rw
DefaultValue=0
PDOMapping=0
Description
AnalogInputGlobalInterruptEnable
Object Code
Variable
Mapping
SDO
Data type
BOOLEAN
Access
rw
Default value
FALSE
Object Code
Variable
Feature
Description / Value
EDS
Name
AI_UPPER_LIMIT
[MxSubExt6424]
ParameterName=AI_UPPER_LIMIT
ObjectType=0x7
DataType=0x0004
AccessType=rw
DefaultValue=0x00000000
HighLimit=0x0000FFFF
PDOMapping=0
Count=8
Description
Analog Input Interrupt Upper Limit Integer
Object Code
ARRAY
Mapping
SDO
Data type
INTEGER32
Sub index
01 … FE
hex
Access
rw
Default value
00000000
hex
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...