7 Product-specific CAN objects XN300 slice modules
7.16 XN-322-8AI-I
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
199
Product-specific CANopen objects
Manufacturer-specific objects
Index range for the XN-322-8AI-I module: x090 to x09F
Index
(hex)
Data Type
Name
Function
Mapping
Access
0x6401
INTEGER16
I-WORD
Read Analog Input 16-bit
Default
ro
PDO
0x6421
UNSIGNED8
AI_INTERRUPT_TRIGGER_SELECTION
Analog Input Interrupt Trigger Selection
–
rw
SDO
0x6423
BOOLEAN
AnalogInputGlobalInterruptEnable
Analog Input Global Interrupt Enable
–
rw
SDO
0x6424
INTEGER32
AI_UPPER_LIMIT
Analog Input Interrupt Upper Limit Integer
–
rw
SDO
0x6425
INTEGER32
AI_LOWER_LIMIT
Analog Input Interrupt Lower Limit Integer
–
rw
SDO
0x6426
UNSIGNED32
AI_DELTA_VALUE
Analog Input Interrupt Delta Unsigned
–
rw
SDO
0x6427
UNSIGNED32
AI_NEGATIVE_DELTA_VALUE
Analog Input Interrupt Negative Delta Unsigned
–
rw
SDO
0x6428
UNSIGNED32
AI_POSITIVE_DELTA_VALUE
Analog Input Interrupt Positive Delta Unsigned
–
rw
SDO
Index
(hex)
Data Type
Name
Function
Mappin
g
Access
0x1027
UNSIGNED16
ModuleD
Module Identification Number
Number (Object 0x1027)”, page 76
–
ro
SDO
0x3090
UNSIGNED16
ModuleDiag
Module Diagnostic Messages
Manual
ro
PDO
0x3091
INTEGER16
InputChannel1
Input Channel 1
Manual
ro
PDO
0x3092
INTEGER16
InputChannel2
Input Channel 2
Manual
ro
PDO
0x3093
INTEGER16
InputChannel3
Input Channel 3
Manual
ro
PDO
0x3094
INTEGER16
InputChannel4
Input Channel 4
Manual
ro
PDO
0x3095
INTEGER16
InputChannel5
Input Channel 5
Manual
ro
PDO
0x3096
INTEGER16
InputChannel6
Input Channel 6
Manual
ro
PDO
0x3097
INTEGER16
InputChannel7
Input Channel 7
Manual
ro
PDO
0x3098
INTEGER16
InputChannel8
Input Channel 8
Manual
ro
PDO
0x3099
UNSIGNED16
WireBreakDiag
Wire Break Diagnostic Messages
Manual
ro
PDO
0x4001
VISIBLE
STRING
SerialNumber
Number (Object 0x4001)”, page 78
–
const
SDO
0x4004
UNSIGNED8
UserLEDControl
User LED Control
User LED Control (Object 0x4004)”, page
81
–
rw
SDO
0x400C
VISIBLE
STRING
ProductName
Product Name
–
ro
SDO
0x4090
UNSIGNED16
FirmwareVersion
Firmware Version
-
ro
SDO
0x5090
UNSIGNED16
ChannelMeasuringConfig
Channel Measuring Configuration
–
rw
SDO
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...