Configurable FlexPower Gateway with sinking discrete I/O

For additional information, updated
documentation, and accessories, re-
fer to Banner Engineering's website, 

www.bannerengineering.com/sure-
cross

.

The SureCross

®

 wireless system is a radio frequency network with integrated I/O that can oper-

ate in most environments and eliminate the need for wiring runs. Wireless networks are formed
around a Gateway, which acts as the wireless network master device, and one or more Nodes.

• Wireless industrial I/O device with up to 12 sinking discrete inputs or outputs. Default config-

uration is set to 6 inputs and 6 outputs (without bit-packing)

• Selectable transmit power levels of 250 mW or 1 Watt for 900 MHz models and 65 mW for

2.4 GHz models

• Power options allow for +10 to 30V dc or solar for low power applications; this model is not

recommended for DX81 or DX81P6 battery-powered operations

• DIP switches for user configuration
• Modbus serial interface
• Site Survey analyzes the network’s signal strength and reliability and displays the results on

the Gateway's LCD

• Frequency Hopping Spread Spectrum (FHSS) technology and Time Division Multiple Access

(TDMA) control architecture ensure reliable data delivery within the unlicensed Industrial,
Scientific, and Medical (ISM) band

• Transceivers provide bidirectional communication between the Gateway and Node, including

fully acknowledged data transmission

• Lost RF links are detected and relevant outputs set to user-defined conditions

Models

Frequency

Power

I/O

DX80G9M2S-P7

900 MHz ISM
Band

+10 to 30V dc or solar power (this model is
not recommended for DX81 or DX81P6 bat-
tery-powered operation)

Discrete I/O: Up to 12 sinking inputs or up to 12
NMOS sinking outputs (for a total of 12 I/O)
(Default configuration is 6 IN and 6 OUT, without
bit-packing)

DX80G2M2S-P7

2.4 GHz ISM
Band

DX80...C (IP20; NEMA 1) models are also available. To order this model with an IP20 housing, add a C
to the end of the model number: DX80G9M2S-P7C.

WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious
injury or death.
 This device does not include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause either an energized or de-
energized sensor output condition.

CAUTION: Never Operate 1 Watt Radios Without Antennas
To avoid damaging the radio circuitry, never power up SureCross Performance or SureCross MultiHop (1
Watt) radios without an antenna.

SureCross Performance FlexPower Gateway

 

 

P/N 155285_web
Rev. E

9/17/2013

Содержание SureCross Performance FlexPower DX80G9M2S-P7

Страница 1: ...thin the unlicensed Industrial Scientific and Medical ISM band Transceivers provide bidirectional communication between the Gateway and Node including fully acknowledged data transmission Lost RF link...

Страница 2: ...ion Tool The User Configuration Tool UCT software runs on any Windows machine and uses as converter cable to connect your Gateway to the computer The User Configuration Tool UCT offers an easy way to...

Страница 3: ...the cable plugs into 3 Gently unplug the ribbon cable from the board mounted into the bottom housing 4 Remove the black cover plate from the bottom of the device s cover The DIP switches are located...

Страница 4: ...tions shown in the DIP Switch Settings table Transmit Power Levels The 900 MHz radios can be operated at 1 watt 30 dBm or 250 mW 24 dBm While the radios operate in 1 Watt mode they cannot communicate...

Страница 5: ...r connection V Ground dc common connection For the default configuration of 6 IN and 6 OUT use IO 1 through 6 to wire the inputs and IO 7 through 12 to wire the outputs When using the DIP switches to...

Страница 6: ...O1 to IO12 10 10 10 Node 16 Non Bit Packed Discrete OUT de pending on DIP switch configuration 11 11 11 Node 16 12 12 12 Node 16 13 13 13 Node 16 14 14 14 Node 16 15 15 15 Node 16 Control Message 16 1...

Страница 7: ...01 00 Input Point 0 0 0 0 0 0 0 IN 5 IN 4 IN 3 IN 2 IN 1 Parameter Data 0 0 0 0 0 OUT 7 OUT 6 OUT 5 OUT 4 OUT 3 OUT 2 OUT 1 Defining Inputs and Outputs Using the UCT To configure either a Gateway or...

Страница 8: ...and line of sight To determine the range of your wire less network perform a Site Survey Power 10 30V dc or 3 6 5 5V dc low power option Out side the USA 12 24V dc 10 or 3 6 5 5V dc low power option 9...

Страница 9: ...ting Not included with IP20 DX80 C models BWA HW 001 Mounting Hardware Kit containing four M5 0 8 x 25mm SS screws four M5 0 8 x 16mm SS screws four M5 0 8mm SS hex nuts and four 8 32 x 3 4 SS bolts B...

Страница 10: ...any product of its manufacture which at the time it is returned to the factory is found to have been defective during the warranty period This warranty does not cover damage or liability for misuse ab...

Отзывы: