Inputs
Outputs
Discrete Inputs
Rating: 3 mA max current at 30V dc
Sample Rate: Up to 62.5 milliseconds
Report Rate: On change of state
ON Condition (NPN): Less than 0.7V
OFF Condition (NPN): Greater than 2V or open
Discrete Outputs
Update Rate: Up to 62.5 milliseconds
Output State Following Timeout: OFF
ON Condition (NMOS): Less than 0.7V
OFF Condition (NMOS): Open
Discrete Output Rating (12 I/O NMOS)
Less than 100 mA max current at 30V dc
ON-State Saturation: Less than 0.7V at 20 mA
Communication
Environmental
Hardware (RS-485)
Interface: 2-wire half-duplex RS-485
Baud rates: 9.6k, 19.2k (default), or 38.4k
Data format: 8 data bits, no parity, 1 stop bit
Protocol
Modbus RTU
Ratings
Rating for DX80 models: IEC IP67; NEMA 6; (See UL
section below for any applicable UL specifications)
Rating for DX80...C models: IEC IP20; NEMA 1
Conditions
Operating Temperature: −40 to +85 °C (Electronics);
−20 to +80 °C (LCD)
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)
Shock and Vibration
IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.
Included with Model
The following items ship with the DX80 radios.
• BWA-HW-002: DX80 Access Hardware Kit, containing four PG-7 plastic threaded plugs, four PG-7 nylon gland fittings, four PG-7 hex
nuts, one 1/2-inch NPT plug, and one 1/2-inch nylon gland fitting. (Not included with IP20 DX80...C models)
• BWA-HW-001: Mounting Hardware Kit, containing four M5-0.8 x 25mm SS screws, four M5-0.8 x 16mm SS screws, four M5-0.8mm
SS hex nuts, and four #8-32 x 3/4" SS bolts
• BWA-HW-003: PTFE tape
• BWA-9O2-C (900 MHz) or BWA-2O2-C (2.4 GHz): Antenna, 2 dBd Omni, Rubber Swivel RP-SMA Male. (Not included with Internal
antenna models)
• Quick Start Guide (128185 for DX80 Gateways or 152653 for MultiHop models)
• MQDC1-506: 5-Euro (single ended) straight cable, 2m (Not included with FlexPower devices)
• BWA-HW-011: IP20 Screw Terminal Headers (2 pack) (Included only with the IP20 DX80...C models)
Warnings
Antenna Installations. Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna
configurations installed without surge suppressors invalidate the manufacturer's warranty. Keep the ground wire as short as possible and make all
ground connections to a single-point ground system to ensure no ground loops are created. No surge suppressor can absorb all lightning strikes; do
not touch the SureCross
®
device or any equipment connected to the SureCross device during a thunderstorm.
Exporting SureCross Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Custom-
ers who want to re-export this product to a country other than that to which it was sold must ensure the device is approved in the destina-
tion country. A list of approved countries appears in the Radio Certifications section of the product manual. The SureCross wireless products were
SureCross Performance FlexPower Gateway
P/N 155285_web
Rev. E
www.bannerengineering.com - tel: 763-544-3164
9