Wire No.
Wire Color
1
2
3
4
5
1
Brown
10 to 30V dc
2
White
RS485 / D1 / B / +
3
Blue
dc common (GND)
4
Black
RS485 / D0 / A / –
5
Gray
3.6 to 5.5V dc
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the communication
pins (Tx/Rx) causes permanent damage. For FlexPower devices, do not apply more than 5.5V to the B+ terminal.
Terminal Label Gateway, DX85
10–30V dc Powered Nodes
Battery Powered Nodes
V+
10–30V dc
10–30V dc
Tx/+
RS485 / D1 / B / +
V-
dc common (GND)
dc common (GND)
dc common (GND)
Rx/-
RS485 / D0 / A / -
B+
3.6–5.5V dc
Terminal Blocks and Wiring (12 Sinking I/O Models)
IOx. Input or output (depending on configuration)
GND. Ground/dc common connection.
PWR. Power, 10–30V dc power connection.
NC. No connection (Nodes only)
RX/-. Serial comms line for Gateways and DX85s only. No connec-
tion for Nodes. (Gateway and DX85 models)
TX/+. Serial comms line for Gateways and DX85s only. No connec-
tion for Nodes (Gateway and DX85 models)
V+. Power, 10–30V dc power connection.
V-. Ground/dc common connection.
For the default configuration of 6 IN and 6 OUT, use IO 1 through 6 to wire the inputs and IO 7 through 12 to wire the outputs.
When using the DIP switches to configure the input and output selection, wire the inputs beginning with IO1. After all inputs are wired,
begin using the remaining IOx as outputs. For example, if you are using 10 inputs and 2 outputs, use terminals IO1 through 10 for the
inputs and terminals IO 11 and 12 for the outputs.
Discrete Input Wiring for NPN Sen-
sors
Discrete Output Wiring (NPN or NMOS)
DIx
GND
dc common
DOx
GND
PWR
10-30V dc
Load
dc common
The DIx and DOx of these wiring diagrams
correspond to the IOx on the terminal
block.
LED Behavior for the Gateways
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. When testing communication
between the Gateway and Node, all radios and antennas should be at least two meters apart or the communications may fail.
LED 1
LED 2
Gateway Status
(solid green)
Power ON
(flashing red)
(flashing red)
Device Error
SureCross Performance FlexPower Gateway
P/N 155285_web
Rev. E
www.bannerengineering.com - tel: 763-544-3164
5