5 Connecting the PLC to the gateway using CODESYS
5.3 Configuring the system with XSOFT-CODESYS-3
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
63
–
If the "Start Slaves" function is enabled, the CANopen manager
will start the slaves. If the option is disabled, the slaves will have
to be started by the application.
Figure 41:
CAN parameters for CANopen manager
Setting the baud rate for the CANopen manager
The baud rate for the CANopen manager (XC-152 in this example) and the
baud rate for the CANopen device (XN-312-GW-CAN in this case) must
match.
The maximum bus length must be used as the basis for determining the
maximum transfer rate (
Section “ Maximum cable length (m)”, page 36).
The transfer rate for the XN-312-GW-CAN gateway needs to be set using the
corresponding DIP switches (
Follow the steps below to set the transfer rate for the CANopen manager:
▶
In the "Devices" configuration structure, double-click on <CANbus (CAN-
bus)>.
▶
Open the "CANbus" tab and select the baud rate you want, e.g.,
<125000>.
Figure 42:
CANopen manager baud rate
→
For more detailed information, please refer to the online help for
CODESYS, which can be opened by pressing the <F1> function
key.