7 Product-specific CAN objects XN300 slice modules
7.19 XN-322-4AIO-U2
244
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.19.11 Module Diagnostic Messages (Object 0x31A0)
Object 0x31A0
contains status information on the module's general operat-
ing status.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Byte 1:
Sub-Index 1
≦
n
≦
254
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Feature
Description / Value
EDS
Name
ModuleDiag
[MxSubExt31A0]
ParameterName=ModuleDiag
ObjectType=0x7
DataType=0x0006
AccessType=ro
PDOMapping=1
Count=1
Description
Module Diagnostic Messages
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
ro
7
6
5
4
3
2
1
0
–
–
–
Data bit
Desig-
nation
Description
0
reserved
1
0 = sync OK
1 = no sync
2
0 = OK
1 = FLASH Data CRC Error
3
0 = OK
1 =RAM Data CRC Error
4
0 = OK
1 = Inconsistent FLASH Data
5 – 7
reserved