7 Product-specific CAN objects XN300 slice modules
7.19 XN-322-4AIO-U2
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
243
Design of the data bytes:
7.19.10 Output Channel x (Object 0x21A0 bis 0x21A1)
Objects 0x21A0 to 0x21A1 transmit the digital value of the channels' analog
signal outputs.
Design of the data bytes:
Feature
Description / Value
EDS
Name
AI_POSITIVE_DELTA_VALUE
[MxSubExt6428]
ParameterName=AI_POSITIVE_DELTA_VALUE
ObjectType=0x7
DataType=0x0007
AccessType=rw
DefaultValue=0x00000000
HighLimit=0x0000FFFF
PDOMapping=0
Count=2
Description
Analog Input Interrupt Positive Delta Unsigned
Object Code
ARRAY
Mapping
SDO
Data type
UNSIGNED32
Sub index
01 … FE
hex
Access
rw
Default value
00000000
hex
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
LSB
3 Byte
Byte 2
Sub index
1
≦
n
≦
254
B31
B30
B29
B28
B27
B26
B25
B24
B23
B22
B21
B20
B19
B18
B17
B16
MSB
LSB
Feature
Description / Value
EDS
Name
Output Channel x
[MxSubExt21Ax]
ParameterName=OutputChannelx
ObjectType=0x7
DataType=0x0003
AccessType=rww
PDOMapping=1
Count=1
Description
OutputChannel1
Object 0x21A0
OutputChannel2
Object 0x21A1
Object Code
ARRAY
Mapping
PDO , MANUAL
Data type
INTEGER16
Sub index
01 … FE hex
Access
rww
Default value
0 x 0000 hex
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...