7 Product-specific CAN objects XN300 slice modules
7.5 XN-322-20DI-PCNT
120
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
7.5.1 Read Digital Input 8-Bit (Object 0x6000)
Object 0x6000 represents the digital value of the channels' digital input val-
ues. The object's data is automatically entered into the transmit PDOs
(default mapping).
Design of the data bytes:
7.5.2 Digital Inputs x_y (Object 0x3020 to 0x3022)
Objects 0x3020 to 0x3022 represent the channels' formatted digital input
values.
Design of the data bytes:
Byte 0:
Feature
Description / Value
EDS
Name
I-BYTE
[MxSubExt6000]
ParameterName=I-BYTE
ObjectType=0x7
DataType=0x0005
AccessType=ro
PDOMapping=1
Count=3
Description
Read Digital Input 8-Bit
Object Code
VAR
Mapping
PDO
Default
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
ro
Byte 0:
Sub index
1
≦
n
≦
254
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Feature
Description
Value
EDS
Name
Read Digital Input x_y
[MxSubExt302x]
ParameterName=Inputx_y
ObjectType=0x7
DataType=0x0005
AccessType=ro
PDOMapping=1
Count=1
Description
Input1_8
3020
Input9_16
3021
Input17_20
3022
Object Code
VAR
Mapping
PDO
Manual
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
ro
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...