10 Appendix
10.3 Technical Data
374
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
Potential isolation between supply and field
bus
Yes
Insulation test voltage
U
i
V AC
500
Measurement of the clearance and creepage
distance
IEC/EN 61131-2
CANopen – Baud rates
kBps
10, 20, 50, 125, 250, 500, 1000
Electromagnetic compatibility (EMC)
Overvoltage category
II
Pollution degree
2
Electrostatic discharge (IEC/EN 6113-2:2008,
ESD)
Air discharge (Level 3)
kV
8
Contact discharge (Level 2)
kV
4
Electromagnetic fields (IEC/EN 61131-
2:2008)
1
(80 …. 1000) MHz
V/m
10
(1.4 … 2) GHz
V/m
3
(2 … 2.7) GHz
V/m
1
Radio interference suppression
EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cables
kV
2
CANopen bus cables
kV
1
Surge (IEC/EN 61131-2:2008, Level 1)
Supply
kV
0.5
CAN
kV
1
Radiated RFI (IEC/EN 61131-2:2008, level 3)
V
10
CANopen gateway
XN-312-GW-CAN