7 Product-specific CAN objects XN300 slice modules
7.24 XN-322-1DCD-B35
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
325
7.24.12 Module Diagnostic Messages (Object 0x30EA)
Object 0x30EA contains status information on the module's general operat-
ing status.
Design of the data bytes:
Byte 0:
Feature
Description / Value
EDS
Name
ModuleDiag
[MxSubExt30EA]
ParameterName=ModuleDiag
ObjectType=0x7
DataType=0x0006
AccessType=ro
PDOMapping=1
Count=1
Description
Module Diagnostic Messages
Object Code
ARRAY
Mapping
PDO
Manual
Data type
UNSIGNED16
Sub index
01 … FE
hex
Access
ro
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
reserved
Data bit
Desig-
nation
Description
0
0 = OK
1 = Supply Voltage NOK
1
0 = OK
1 = no sync
2
0 = OK
1 = FLASH Data CRC Error
3
0 = OK
1 = RAM Data CRC Error
4
0 = OK
1 = Inconsistent FLASH Data
5 – 7
reserved