5 Connecting the PLC to the gateway using CODESYS
5.3 Configuring the system with XSOFT-CODESYS-3
68
Gateway XN-312-GW-CAN
06/16 MN050003-EN www.eaton.eu
▶
Double-click on the CANopen device and open the "CANopen Remote
Device" tab.
▶
Enable the "Enable Expert Settings" checkbox.
▶
Disable the "Autoconfig PDO Mapping" checkbox.
▶
Open the "PDO Mapping" tab.
Manually adding a PDO
The pane on the left will show the receive PDOs (RPDOs), while the pane on
the right will show the send PDOs (TPDOs).
▶
If necessary, you can add a new PDO by clicking on the "Add PDO..." but-
ton.
Do not exceed the maximum number of 16 RPDOs and 16 TPDOs! The
program will show an error message otherwise!
▶
Double-click on a PDO that has been added, e.g., "TransmitPdoParame-
ter," and configure its properties.
Figure 48:
Selecting a transmission type for the manually mapped PDO
Defining the process data for a PDO
▶
Select the PDO you want, e.g., "TransmitPdoParameter."
▶
Click on the "Add Mapping..." button.
▶
In the "Select item from object directory" dialog box, select the item you
want, e.g., "Counter1:XN_322_20DI_PCNT"
▶
Confirm with OK.
The item you selected will be added to the PDO.
Figure 49:
Manually added TPDO with process data for counter 1