7 Product-specific CAN objects XN300 slice modules
7.20 XN-322-8AIO-U2
Gateway XN-312-GW-CAN 06/16 MN050003-EN
www.eaton.eu
253
7.20.2 Write Analog Output 16-Bit (Object 0x6411)
Object 0x6411 transmits the digital value of the channels' analog signal out-
puts. The object's data is automatically entered into the receive PDOs
(default mapping).
Design of the data bytes:
7.20.3 Analog Input Interrupt Trigger Selection (Object 0x6421)
Object 0x6421 defines which events will trigger an interrupt for the corre-
sponding channel so that the channel's analog input value (object 0x6401)
will be transmitted when the event occurs.
Design of the data bytes:
Byte 0:
Sub-Index 1
≦
n
≦
254
Feature
Description / Value
EDS
Name
Write Analog Output 16-Bit
[MxSubExt6411]
ParameterName=Q-WORD
ObjectType=0x7
DataType=0x0003
AccessType=rww
PDOMapping=1
Count=4
Description
Q-WORD
Object Code
ARRAY
Mapping
PDO
Default
Data type
INTEGER16
Sub index
01 … FE
hex
Access
rww
Default value
00
hex
1 Byte
Byte 0:
Sub index
1
≦
n
≦
254
B15
B14
B13
B12
B11
B10
B9
B8
B7
B6
B5
B4
B3
B2
B1
B0
MSB
LSB
Feature
Description / Value
EDS
Name
Analog Input Interrupt Trigger Selection
[MxSubExt6421]
Parameter-
Name=AI_INTERRUPT_TRIGGER_SELECTIO
N
ObjectType=0x7
DataType=0x0005
AccessType=rw
DefaultValue=7
LowLimit=0
HighLimit=31
PDOMapping=0
Count=4
Description
AI_INTERRUPT_TRIGGER_SELECTION
Object Code
ARRAY
Mapping
SDO
Data type
UNSIGNED8
Sub index
01 … FE
hex
Access
rw
Default value
07
hex
Содержание XN-312-GW-CAN
Страница 1: ...Manual CANopen Gateway XN 312 GW CAN 06 16 MN050003 EN ...
Страница 4: ...II ...
Страница 14: ...10 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton com ...
Страница 374: ...9 What Happens If 370 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...
Страница 388: ...384 Gateway XN 312 GW CAN 06 16 MN050003 EN www eaton eu ...