Services
Modbus gateway
Digi Connect IT® 16/48 User Guide
410
This will configure the gateway to deliver all messages that have the Modbus server
address address of 20 to the device with address 10.
i. Repeat the above instructions for additional clients.
6. Save the configuration and apply the change:
(config)> save
Configuration saved.
>
7. Type
exit
to exit the Admin CLI.
Depending on your device configuration, you may be presented with an
Access selection
menu
. Type
quit
to disconnect from the device.
Show Modbus gateway status and statistics
You can view status and statistics about location information from either the WebUI or the command
line.
WebUI
1. Log into the Connect IT 16/48 WebUI as a user with Admin access.
2. On the menu, select
Status
>
Modbus Gateway
.
The
Modbus Gateway
page appears.
Statistics related to the Modbus gateway server are displayed. If the message
Server
connections not available
is displayed, this indicates that there are no connected clients.
n
To view information about Modbus gateway clients, click
Clients
.
n
To view statistics that are common to both the clients and server, click
Common
Statistics
.
n
To view configuration details about the gateway, click the
(configuration) icon in the
upper right of the gateway's status pane.
Command line
1. Log into the Connect IT 16/48 command line as a user with Admin access.
Depending on your device configuration, you may be presented with an
Access selection
menu
. Type
admin
to access the Admin CLI.
2. Use the
command at the system prompt:
> show modbus-gateway
Server Connection
IP Address
Port
Uptime
-----------------
-----------
-----
------
modbus_socket
10.45.1.139
49570
6
modbus_socket
10.45.1.139
49568
13
Client
Uptime
--------------------
------
modbus_socket_41
0