3 - 1 9
3
Operation Modes
MAIN
LOAD
BYPA.
Q1
Q2
Q4
Q3
Batteries
Rectifier
Inverter
Static Switch
Q5
(Figure 3-18: Manual Bypass Mode Diagram_ Dual Input Single Unit)
3.2.5 ECO Mode_ Dual Input_ Single Unit
To activate ECO mode, please refer to
6.2.5 ECO Mode Start-up Procedures
,
7.6 Main
Screen
and
7.10.2 Mode Setting
.
In ECO mode, when the bypass AC source’s input voltage and frequency are within the
setup range (default: voltage ±10% and frequency ±3Hz), the UPS works in Bypass mode;
otherwise, the UPS runs in On-Line mode. For ECO mode diagram, please see
Figure 3-19
.
During ECO mode, the UPS’s tri-color LED illuminates green and the text '
ECO
' appears in
the upper right corner of the screen.
MAIN
LOAD
BYPA.
Q1
Q2
Q4
Q3
Batteries
Rectifier
Inverter
Static Switch
Q5
(Figure 3-19: ECO Mode Diagram_ Dual Input Single Unit)