3 - 3 0
Modulon DPH Series
3.4
Common Battery (Only for Parallel UPSs connecting to
the Same External Battery Cabinet(s))
NOTE:
1. The 'common battery' information in this chapter is not applicable to the UPS
using lithium-ion batteries. For relevant information, please refer to the user
manual of the lithium-ion batteries and contact Delta customer service.
2. Whether you use the lead-acid batteries or the lithium-ion batteries, please
contact Delta customer service for any battery/ battery cabinet’s setup and
FRQ¿JXUDWLRQV
To save on your costs and installation space, the parallel UPSs can share their connected
external battery cabinet(s). For common battery application, please install a protective
device between each parallel UPS and its connected external battery cabinet(s). For
relevant information about the protective device, please refer to
5.6 External Battery
Cabinet Connection Warnings
. Please see
Figure 3-29
for two parallel UPSs sharing one
external battery cabinet as an example.
If the parallel UPSs share the external battery cabinet(s), you should use the LCD to set up
relevant parameters such as '
Battery Type
', '
Capacity
', '
Battery Strings
', '
Float Charge
Voltage
', '
Equalized Charge Voltage
'
*
1
, '
Charge Current (Max)
', etc. For more information,
please refer to
7.10.4 Battery & Charging Setting
.
NOTE:
1. For common battery application, please use the LCD to set each UPS’s
float charge voltage (default: 272V) the same, each UPS’s equalized charge
voltage
*
1
(if applicable, default: 280V) the same, and each UPS’s battery strings
and charge current (Max) even. For example:
A. When (1) two UPSs are paralleled and share one external battery cabinet,
(2) the lead-acid batteries are used, (3) the battery capacity is 200AH, (4)
there are a total of 4 battery strings, and (5) the charge current (Max) is 80A,
please use the LCD to set each UPS’s '
Battery Type
' as '
VRLA
', '
Capacity
'
as 200AH, '
Battery Strings
' as 2, and '
Charge Current (Max)
' as 40A.
B. When (1) three UPSs are paralleled and share one external battery cabinet,
(2) the lead-acid batteries are used, (3) the battery capacity is 300AH, (4)
there are a total of 3 battery strings, and (5) the charge current (Max) is 90A,
please use the LCD to set each UPS’s '
Battery Type
' as '
VRLA
', '
Capacity
'
as 300AH, '
Battery Strings
' as 1, and '
Charge Current (Max)
' as 30A.
2.
*
1
The item '
Equalized Charge Voltage
' mentioned above will change into
'
Restore Voltage
' if you use the Delta lithium-ion batteries with the optional
multifunctional communication card (MFC) being installed in the smart slot
shown in
Figure 4-15
. For relevant information, please refer to
7.10.4 Battery
& Charging Setting
.
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......