6 - 3 7
6
UPS Operation
%\SDVV0RGH7XUQRႇ3URFHGXUHV
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOO
parallel ones, please contact service personnel.
1
In Bypass mode, the LCD shows the following screen (
Figure 6-51)
and the tri-color
LED indicator illuminates yellow. For the tri-color LED indicator location, please refer
to
Figure 2-12
.
Bypass
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
(Figure 6-51: Bypass Mode Screen)
2
Switch
OFF
the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
After that, the UPS will run in Standby mode.
3
1RZHDFKSRZHUPRGXOHSHUIRUPV'&%86GLVFKDUJLQJDQGLWV/('LQGLFDWRUÀDVKHV
JUHHQ$IWHUGLVFKDUJLQJHDFKSRZHUPRGXOH¶V/('LQGLFDWRUZLOOEHRႇ
4
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED
LQGLFDWRUZLOOEHRႇ
5
Switch
OFF
every external battery cabinet’s breaker (Q5).
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......