6 - 7
6
UPS Operation
8
After selection of '
YES
' to start up the UPS’s inverter, each power module will start
up and perform self-inspection. At the same time, the system begins synchronization
with the bypass AC source. After the self-inspection is completed, the UPS will
automatically transfer to run in On-Line mode, the tri-color LED indicator will illuminate
green and the following screen will appear. For the location of the tri-color LED
indicator, please refer to
Figure 2-12
.
On-Line
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
(Figure 6-5: On-Line Mode Screen)
6.2.2 Battery Mode Start-up Procedures
WARNING:
1. For parallel units, please follow
6.2.3 Bypass Mode Start-up Procedures
to turn on each parallel UPS. After confirming that parallel operation works
normally, follow the procedures below step by step.
2. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOO
parallel ones, please contact service personnel.
1
Ensure that the Manual Bypass Breaker (Q3) is in the
OFF
position.
2
Switch
ON
every external battery cabinet’s breaker (Q5).
3
Switch
ON
the Output Breaker (Q4).
4
Press any of the
BATT. START
buttons (see
Figure 7-2
) for one second and release
it. After that, each auxiliary power card’s LED indicator will illuminate green and the
following status will occur simultaneously.
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......