5 - 2 3
5
Installation and Wiring
NOTE:
1. You can adjust the charge current from 1 A to the maximum. Each adjustment
level is 1 A.
For the maximum charge current, please refer to
Table 5-4 ~ Table 5-5
.
Table 5-4: Maximum Charge Current for Environment Temperature below
25°C (77°F)
DPH 20 ~ 80kVA
20kVA
40kVA
60kVA
80kVA
8A
16A
24A
32A
DPH 20 ~ 120kVA
20kVA
40kVA
60kVA
80kVA
100kVA
120kVA
8A
16A
24A
32A
40A
48A
Table 5-5: Maximum Charge Current for Environment Temperature above
25°C (77°F)
DPH 20 ~ 80kVA
20kVA
40kVA
60kVA
80kVA
6A
12A
18A
24A
DPH 20 ~ 120kVA
20kVA
40kVA
60kVA
80kVA
100kVA
120kVA
6A
12A
18A
24A
30A
36A
2. If you need to modify the default charge current setting and default low battery
shutdown setting, please contact your local dealer or service personnel.
3. Follow on-site requirements to choose 12V × 30/ 32/ 34/ 36/ 38/ 40/ 42/ 44
or 46 PCS batteries. Change of the battery quantity will influence the applied
VSHFL¿FDWLRQV)RUEDWWHU\VHOHFWLRQLQVWDOODWLRQDQGUHSODFHPHQWSOHDVHFRQWDFW
your local dealer or customer service.
4. The number of batteries that you set up via the LCD must be the same as that
of on-site installation; otherwise, the batteries will be over charged, not fully
charged or even seriously damaged.
y
Only use the same type of batteries from the same supplier. Never use old, new and dif-
ferent Ah batteries at the same time.
y
The number of batteries must meet the UPS requirements.
y
Do not connect the batteries in reverse.
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......