6 - 3 6
Modulon DPH Series
Battery
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
No
Yes
LOG IN
User
POWER OFF ?
Transfer to Bypass without Protection!
2
WARNING
10:15
May 25,2018
(Figure 6-49: Power off Reminder Screen)
3
After selection of '
YES
', the UPS will shut down the inverter, terminate each power
module’s output and transfer to run in Standby mode. At this moment, the tri-color LED
indicator illuminates yellow and the following screen (
Figure 6-50)
appears. For the tri-
color LED indicator location, please refer to
Figure 2-12
.
Standby
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
0 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
LOG IN
User
2
WARNING
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
(Figure 6-50: Standby Mode Screen)
4
Switch
OFF
the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
5
1RZHDFKSRZHUPRGXOHSHUIRUPV'&%86GLVFKDUJLQJDQGLWV/('LQGLFDWRUÀDVKHV
JUHHQ$IWHUGLVFKDUJLQJHDFKSRZHUPRGXOH¶V/('LQGLFDWRUZLOOEHRႇ
6
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED
LQGLFDWRUZLOOEHRႇ
7
Switch
OFF
every external battery cabinet’s breaker (Q5).
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......