6 - 2 4
Modulon DPH Series
7
Please log in as an
Administrator
. For the
Administrator
password, please contact
service personnel. After login, ensure that you are in the
Administrator
login status
(see
Figure 6-29
).
Bypass
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
Power Flow
Summary
EMS
System Status
10:15
May 25,2018
Administrator Login
ON/ OFF
Button
(Figure 6-29: Main Screen_ Administrator Login & ON/ OFF Button Location)
8
Go
to
SETUP
ĺ
Mode Setting
ĺ
Frequency Conversion
.
WARNING:
Please note that, once you select '
Frequency Conversion
' mode via the
LCD, the UPS will run in Standby mode and the output will be terminated.
Standby
UPS-1.1
MEASUREMENT
Mode Setting
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
MODE SETTING
On-Line
Green
ECO
Energy
Recycle
Frequency
Conversion
Select to change system mode
10:15
May 25,2018
(Figure 6-30: Select Frequency Conversion Mode)
9
Tap the icon (
UPS-1.1
) located in the upper left corner of the screen to go back to the
Main Screen
.
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......