6 - 4 6
Modulon DPH Series
5
Go
to
SETUP
ĺ
Mode Setting
ĺ
On-Line
.
Bypass
UPS-1.1
MODE SETTING
MEASUREMENT
Mode Setting
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
On-Line
Green
ECO
Energy
Recycle
Frequency
Conversion
Select to change system mode
10:15
May 25,2018
(Figure 6-66: Select On-Line Mode)
6
Switch
OFF
the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
After that, the UPS will run in Standby mode.
7
1RZHDFKSRZHUPRGXOHSHUIRUPV'&%86GLVFKDUJLQJDQGLWV/('LQGLFDWRUÀDVKHV
JUHHQ$IWHUGLVFKDUJLQJHDFKSRZHUPRGXOH¶V/('LQGLFDWRUZLOOEHRႇ
8
About 3 minutes later, the UPS will shut down, and the LCD and the tri-color LED
LQGLFDWRUZLOOEHRႇ
9
Switch
OFF
every external battery cabinet’s breaker (Q5).
(QHUJ\5HF\FOH0RGH7XUQRႇ3URFHGXUHV
WARNING:
Energy Recycle mode is only applicable to single input and single unit application.
1
In Energy Recycle mode, the LCD shows the following screen (
Figure 6-67)
and
the tri-color LED indicator illuminates yellow. For the tri-color LED indicator location,
please refer to
Figure 2-12
.