7 - 5 0
Modulon DPH Series
Input Dry
Contact No.
Event Selection
Type
Input Dry Contact 1
Input Dry Contact 2
Input Dry Contact 3
Input Dry Contact 4
Select one of the following events as
the setting for each input dry contact.
1. None
2. Generator status
3. Battery ground fail
4. External battery breaker detection
5. Charge Off (Positive)
6. Charge Off (Negative)
7. Battery Abnormal Shutdown
8. Input Transformer OTW
9. Output Transformer OTW
10. Battery Fuse Open
Set up NO (normally
open) or NC (normally
closed) for each input
dry contact.
Bypass
1
2
3
4
5
6
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
MEASUREMENT
Dry Contact Setting
DRY CONTACT SETTING
INPUT
OUTPUT
Event
Type
Normally Open
Normally Open
Normally Open
Normally Open
Normally Open
Normally Open
None
None
None
None
None
None
10:15
May 25,2018
Input Dry
Contact No.
Event Selection
Type
Output Dry Contact 1
Output Dry Contact 2
Output Dry Contact 3
Output Dry Contact 4
Output Dry Contact 5
Output Dry Contact 6
Select one of the following events as
the setting for each output dry contact.
1. None
2. Load on inverter
3. Load on bypass
4. Load on battery
5. Battery low
6. Battery input abnormal
7. Battery test fail
8. Internal comm. fail
9. External parallel comm. fail (only
applicable to parallel application)
Set up NO (normally
open) or NC (normally
closed) for each input
dry contact.
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......