3 - 1 7
3
Operation Modes
MAIN
LOAD
BYPA.
Q1
Q2
Q4
Q3
Batteries
Rectifier
Inverter
Static Switch
Q5
(Figure 3-16: Battery Mode Diagram_ Dual Input Single Unit)
3.2.3 Bypass Mode_ Dual Input_ Single Unit
When the inverter encounters abnormal situations such as over temperature, overload,
short circuit, abnormal output voltage or low battery, it will automatically shut itself down.
If the UPS detects the bypass AC source is normal, it will automatically switch to Bypass
mode to protect the connected critical loads from power interruption. Please refer to
Figure
3-17
. After the above-mentioned abnormalities are eliminated, the UPS will switch back to
On-Line mode from Bypass mode. During Bypass mode, the UPS’s tri-color LED illuminates
yellow and the text '
Bypass
' appears in the upper right corner of the screen.
MAIN
LOAD
BYPA.
Q1
Q2
Q4
Q3
Batteries
Rectifier
Inverter
Static Switch
Q5
(Figure 3-17: Bypass Mode Diagram_ Dual Input Single Unit)