LCD Display & Settings
7.10.2 Mode Setting
Path:
SETUP
ĺ0RGH6HWWLQJ
After entering the
MODE SETTING
screen
*
1
VKRZQLQWKH¿JXUHEHORZ\RXFDQVHWXSWKH
UPS system mode, of which there are 5 options:
On-Line Mode, Green Mode, ECO Mode,
Energy Recycle Mode
and
Frequency Conversion Mode
. These settings must be carried
RXWE\TXDOL¿HGVHUYLFHSHUVRQQHO3OHDVHFRQWDFW'HOWDFXVWRPHUVHUYLFHIRUDVVLVWDQFH
NOTE:
*
1
means that the
Administrator
password is needed. For password
information, please refer to
7.5 Password Entry
.
Bypass
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
MEASUREMENT
Mode Setting
MODE SETTING
On-Line
Green
ECO
Energy
Recycle
Frequency
Conversion
Select to change system mode
10:15
May 25,2018
Item
Description
On-Line Mode
Set up the UPS in On-Line mode. In On-Line mode, it is the inverter
to supply power to the connected loads.
Green Mode
Set up the UPS in Green mode. In Green mode, it is the inverter to
supply power to the connected loads and the power modules take
turn to rest according to the situation of total load capacity.
ECO Mode
Set up the UPS in ECO mode. In ECO mode, it is the bypass to
supply power to the connected loads. It is suggested that you set
the UPS in ECO mode only when there is stable main AC power.
Otherwise, power supply quality will be compromised.
Energy Recycle
Mode
Set up the UPS in Energy Recycle mode. In Energy Recycle mode,
the full load output can be simulated for the aging test without real
output to the loads.
Содержание Modulon DPH series
Страница 26: ......
Страница 58: ......
Страница 168: ......
Страница 237: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 240: ......
Страница 241: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 246: ......
Страница 247: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 250: ......