background image

Powerware 9355 Parallel UPS
10/15 kVA
User’s Guide

®

Содержание Powerware 9355 Parallel

Страница 1: ...Powerware 9355 Parallel UPS 10 15 kVA User s Guide...

Страница 2: ...sing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil num rique de la classe A respecte toutes les exigences du Reglement sur le mat ri...

Страница 3: ...quipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 33...

Страница 4: ...nstructions This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more infor...

Страница 5: ...el Installation 17 5 Installing Options 27 Powerware Hot Sync CAN Bridge Card 28 6 Stabilizing the Cabinet 33 7 Extended Battery Module Installation 37 8 Operation 41 Control Panel Functions 41 Changi...

Страница 6: ...TABLE OF CONTENTS EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com ii...

Страница 7: ...onfiguration In addition when one UPS is taken out of service for maintenance or is not operating properly a redundant UPS continues to supply uninterrupted power to the critical load A parallel Power...

Страница 8: ...INTRODUCTION EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 2...

Страница 9: ...ectric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or ex...

Страница 10: ...eur uniquement l int rieur dans un lieu d pourvu de mat riaux conducteurs o la temp rature et l humidit ambiantes sont contr l es La temp rature ambiante ne doit pas d passer 40 C Ne pas utiliser prox...

Страница 11: ...l riesgo de incendio o de choque el ctrico instale este SIE en un lugar cubierto con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40...

Страница 12: ...SAFETY WARNINGS EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 6...

Страница 13: ...g the Equipment If any equipment has been damaged during shipment keep the shipping and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover dama...

Страница 14: ...proximate weights are shown in the following table Standard Model Floor Loadings 2 High 3 High Cabinets Powerware 9355 Maximum Weight Point Loading lb in2 kg cm2 2 High UPS 381 lb 173 kg 95 6 7 3 High...

Страница 15: ...y see page 8 Unloading the cabinets requires at least two people to safely remove the cabinets from the pallet To unload three high cabinets or two high EBMs continue to the following section To unloa...

Страница 16: ...Retain the hardware for later use NOTE Be sure to retain the stabilizing bracket and hardware for later re assembly onto the cabinet 3 Remove the front cover from the bottom cabinet to access the fron...

Страница 17: ...emove the two M10 bolts securing the front shipping bracket and remove the bracket If needed adjust the leveling feet to release the bracket Stabilizing Bracket Front Shipping Bracket Shipping Pad M4...

Страница 18: ...ly roll the cabinet toward the rear of the pallet Once the pallet tilts continue rolling the cabinet down the pallet until the cabinet touches the floor see Figure 4 If needed adjust the leveling feet...

Страница 19: ...e shipping pallet 1 Remove the M10 bolt securing the vertical bracket to the pallet see Figure 6 2 Remove and retain the three M4 screws securing the vertical bracket to the UPS Remove the vertical br...

Страница 20: ...d then lift the cover up and off the cabinet 6 Remove the three M10 bolts securing the rear shipping pad to the pallet and remove the shipping pad see Figure 8 NOTE Hold the back of the cabinet so tha...

Страница 21: ...r the bottom edge and snap into place NOTE Be sure to support the front and back of the cabinet when rolling it off the pallet to prevent tipping 9 Slowly roll the cabinet toward the rear of the palle...

Страница 22: ...allel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 16 10 With the cabinet supported slowly pull the pallet away from the cabinet see Figure 10 Figure 10 Removing the Pallet 11 Roll t...

Страница 23: ...personnel such as a licensed electrician should perform the UPS installation and initial startup Risk of electrical shock To hardwire the parallel system 1 Verify that the electrical connections to th...

Страница 24: ...m 18 4 Determine your equipment s grounding requirements according to your local electrical code 5 Remove the parallel tie cabinet front cover see Figure 11 Figure 11 Parallel Tie Cabinet Front Cover...

Страница 25: ...the parallel bypass breaker is in the OFF position see Figure 13 9 Mount the parallel tie cabinet to the wall and install the conduit Figure 13 Parallel Bypass Breaker 10 Verify that each UPS battery...

Страница 26: ...ALLATION EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 20 Battery Circuit Breaker UPS Wiring Access Cover Conduit Landing Plates Figure 14 UPS Rear View...

Страница 27: ...Number of Conduits 208 Input 60A 4 AWG 10 AWG 120 lb in 1 25 conduit 1 220 p 60A 4 AWG 10 AWG 120 lb in 13 5 Nm 1 25 conduit 1 208 Output 6 AWG 10 AWG 120 lb in 1 00 d i 1 220 p 6 AWG 10 AWG 120 lb in...

Страница 28: ...1 Rev A www powerware com 22 Ground Maintenance Bypass Contacts TB2 Figure 15 UPS Terminal Block 3 High Shown 14 Hardwire the output terminations from the UPS to the parallel tie cabinet see Figure 16...

Страница 29: ...ires in the parallel tie cabinet see Figure 15 Connect the black and the red wire to TB2 on the UPS Cap the blue wire NOTE The maintenance bypass contacts are normally open To ensure proper bypass ope...

Страница 30: ...he AC input to the bypass breaker see Figure 18 Line 1 Line 2 Line 3 Figure 18 Bypass AC Input Wiring 20 Verify the phase rotation for each UPS and the bypass input 21 Reinstall the internal cover rem...

Страница 31: ...01 Rev A www powerware com 25 From UPS 4 Output From UPS 3 Output From UPS 2 Output Red Wire open when breaker is open Bypass Input Black Wire common From UPS 1 Output 225A 80A 4X LOAD Blue Wire close...

Страница 32: ...PARALLEL INSTALLATION EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 26 Figure 20 Parallel UPS Schematic...

Страница 33: ...emergency power off REPO relay output contacts or programmable signal inputs refer to the Powerware 9355 UPS 10 15 kVA User s Guide Figure 21 shows the location of the communication options and contro...

Страница 34: ...ivity for operational mode control and metering of a parallel system at any UPS in the system Plug In Terminal Block Figure 22 Powerware Hot Sync CAN Bridge Card To install the Powerware Hot Sync CAN...

Страница 35: ...isted pair on all cards together 4 Wire the factory installed pull chain wiring to Signal Input 2 on each UPS and daisy chain the wiring to each UPS as shown in Figure 24 Be sure to check correct pola...

Страница 36: ...re 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 30 SHIELD CAN H CAN L TX TX 10 9 8 1 7 6 5 4 3 2 NO COM NC ALM RTN ALARM J3 J5 1 2 1 2 1 2 1 2 UPS 1 UPS 2 UPS 3 UPS 4 F...

Страница 37: ...the bottom cover and also the middle cover if 3 high remove a knockout tab in the top edge of the cover for each cable With wire cutters cut either side of the tab and twist down to remove the tab se...

Страница 38: ...vers starting with the bottom cabinet see Figure 26 Hang the top edge of the cover on the cabinet first then lower the bottom edge and snap into place Be sure the cables fit in the access holes in the...

Страница 39: ...t 2 Attach the stabilizing bracket to the bottom of the cabinet rear panel using the retained hardware from the shipping pallet according to the cabinet configuration S For one cabinet see Figure 28 S...

Страница 40: ...ABINET EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 34 M4 Screws Figure 28 Stabilizing Bracket with One Cabinet M4 Screws Figure 29 Stabilizing Bracket...

Страница 41: ...STABILIZING THE CABINET EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 35 M4 Screws Figure 30 Stabilizing Bracket with Three Cabinets...

Страница 42: ...STABILIZING THE CABINET EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 36...

Страница 43: ...In a parallel system each UPS should have the same number of Extended Battery Modules EBMs to ensure equivalent runtimes To install the optional EBM 1 Position the EBM adjacent to the next cabinet 2 V...

Страница 44: ...arallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 38 UPS Battery Connector Rear Ground Strap EBM Battery Circuit Breaker EBM Battery Connector EBM Cable UPS Battery Circuit Breake...

Страница 45: ...et 9 Install the remaining ground straps between each cabinet see Figure 32 10 Reinstall the top front covers removed in Step 8 Hang the top edge of the cover on the cabinet first then lower the botto...

Страница 46: ...EXTENDED BATTERY MODULE INSTALLATION EATON Powerware 9355 Parallel UPS 10 15 kVA User s Guide S 164201601 Rev A www powerware com 40...

Страница 47: ...hutdown and configuring the UPS for Extended Battery Modules EBMs Control Panel Functions The UPS has a four button graphical LCD with backlight It provides useful information about the UPS itself loa...

Страница 48: ...alarm condition See Troubleshooting on page 53 for additional information Changing the Language Press and hold the first button on the left for approximately five seconds to select the language menu...

Страница 49: ...r Output L N and L L Current Frequency Power Battery Voltage Current Runtime Input L N and L L Current Frequency Bypass L N and L L Frequency Control Go to Bypass Mode Transfers the UPS system to inte...

Страница 50: ...lish Elegir idioma Espa ol English Set NominalOutput Voltage Output 120V 208V 127V 220V 120V 208V Relay Config Relay Alarm 1 X Slot 1 1 2 3 4 or X Slot 2 1 2 3 4 Setup Battery Low On Battery On Bypass...

Страница 51: ...UPS 32 models 4 strings for UPS 64 models Battery Capacity 1 through 65535 watts per cell 34 W cell Battery Low Alarm Level 1 750 through 1 950 volts per cell 1 880 V cell Bypass Voltage High Limit 1...

Страница 52: ...sabled Enabled Reset Custom Event Settings 0 through 32 Total 0 32 Auto Output Configuration Enabled Disabled Enabled for initial startup Disabled after initial startup Initial Startup Startup and ope...

Страница 53: ...Press the button twice to select the User Settings menu 4 Using the button scroll to the Number of Battery Strings option and press the button 5 Use the or buttons to select the number of strings acc...

Страница 54: ...anel display and then press the button to select the TURN UPS ON OFF menu 3 Press the button to select the System Off option press the button 4 Confirm the selection Press and hold the button for thre...

Страница 55: ...button 4 Confirm the selection Press and hold the button for three seconds until the UPS stops beeping The input contactor opens 5 Switch the UPS battery circuit breaker to the OFF position The UPS i...

Страница 56: ...parallel tie cabinet to the ON position 6 Verify that no alarms appear on the UPS front panel display If the indicator is flashing do not proceed until all alarms are clear Check the UPS status from...

Страница 57: ...to internal Bypass mode S Using the button on the front panel display scroll to the Control menu option and press the button S Press the button to select the Go to Bypass Mode option The and indicato...

Страница 58: ...t internal bypass to return the parallel system to Normal mode 3 Set the system to internal Bypass mode S Using the button on the front panel display scroll to the Control menu option and press the bu...

Страница 59: ...every second A utility failure has occurred and the UPS is in Battery mode The UPS is powering the equipment with battery power Prepare your equipment for shutdown Battery Low LED is on Continuous be...

Страница 60: ...nstalled the input circuit breaker is off Verify that the isolation transformer input circuit breaker is on The remote emergency power off REPO switch is active or the REPO connector is missing Reset...

Страница 61: ...bnormal output voltage at startup The UPS breaker on the parallel tie cabinet was not switched to the ON position properly Shut down the UPS where the alarm is indicated Switch the UPS breaker on the...

Страница 62: ...llowing telephone numbers and ask for a UPS technical representative United States 1 800 843 9433 or 1 919 870 3028 Canada 1 800 461 9166 ext 260 All other countries Call your local service representa...