12-28
Diagnostic Message Descriptions
ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
E291 Timeout in EMD Module
Description:
The EMD Modules send the inputs to the base unit in a cyclic telegram. If
this telegram is not sent for 2 cycles, Warning E291 is generated.
The following is valid:
Cycle Time = (number of 1) ms.
If drive enable is set, Error F291 is generated in place of the warning.
Cause:
1. Address switch on the EMD Module is set incorrectly.
2. Faults on the EcoX Bus.
3. EcoX Bus is incorrectly wired.
4. The supply voltage for the EMD Module was turned off.
Remedy:
1. Check the address switch on the EMD Module (for the new address
to be accepted, the supply voltage must be turned on and then off at
the EMD Module).
2. Check EcoX Bus
3. Check the wiring of the EcoX bus
4. Check the supply voltage for the EMD Modules.
E293 Undervoltage in EMD Module
Cause:
The EMD modules of the EcoX bus have a supply voltage of 24 V. If this
voltage drops below 17 V, the undervoltage is signaled at the EMD
module by a red LED (H2) and the warning E293 is generated.
Remedy:
Check the power supply or increase the voltage to the rated voltage of
24 V.
E296 Number of EcoX Slaves incorrect
The number of EcoX Slaves must be entered in Parameter B014, EMD
Configuration for the EcoX Master. If the master notices that the number
of EcoX slaves does not correspond with the parameterized value when
scanning the slaves, warning E296 is generated. The EcoX master
cyclically scans the EcoX slaves until their number corresponds with the
parameterized number of EcoX slaves. If warning E296 is activated and
you try to set the controller enable signal, error F296 is generated.
Cause:
1. The EcoX bus has not been correctly wired
2. The EcoX bus has not been parameterized in an EcoX slave and/or
master
3. The EcoX bus is disturbed
4. The supply voltage of the EcoX slaves was cut off
Содержание Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS
Страница 18: ...XVI Table of Contents ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P ...
Страница 58: ...4 20 General Instructions for Start Up ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 187: ...ECODRIVE03 FL 04VRS Functions 8 41 DOK ECODR3 FL 04VRS FK01 EN P fp5007fj_AE WMF Fig 8 22 Control Loop ...
Страница 241: ...ECODRIVE03 FL 04VRS Parameters 9 29 DOK ECODR3 FL 04VRS FK01 EN P SIC_2_AE WMF Fig 9 12 Signal Control ...
Страница 348: ...11 18 Command Communications ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 418: ...13 4 Connectors ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 469: ...ECODRIVE03 FL 04VRS IDS Accessories 16 3 DOK ECODR3 FL 04VRS FK01 EN P IDS_mas_AE WMF Fig 16 5 IDS Dimensions ...
Страница 470: ...16 4 IDS Accessories ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 489: ......