ECODRIVE03-FL*-04VRS
Interface
10-17
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
Communications via RS485 Interface
Features
Communication via the RS485 interface makes it possible to implement a
serial bus with the following data:
•
Up
to
8 drives can be connected to one bus master.
•
Transmission rates of:
2400
baud ASCII
4800
baud
ASCII
9600
baud
ASCII / SIS
19200 baud
ASCII / SIS
•
Maximum transmission path: 500m
•
Half duplex mode over a 2-wire line
•
8-bit
ASCII protocol or 8-bit SIS protocol
•
Parity bit: none, even, odd
•
one stop bit
Fs0005d1_AE.WMF
Fig. 10-15 Data Exchange of Drive Groups from an Operator Console
Transmission Protocols
When the 24V supply voltage is switched on, the data set in Parameters
B001, B002, B009 and B010 are used as the communications
parameters. If these settings do not correspond to the data in the
programming unit, the S1 button on the programming module can be
used to set the default transmission parameters. See also: "Initial Startup"
Chapter, S1 Button.
Содержание Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS
Страница 18: ...XVI Table of Contents ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P ...
Страница 58: ...4 20 General Instructions for Start Up ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 187: ...ECODRIVE03 FL 04VRS Functions 8 41 DOK ECODR3 FL 04VRS FK01 EN P fp5007fj_AE WMF Fig 8 22 Control Loop ...
Страница 241: ...ECODRIVE03 FL 04VRS Parameters 9 29 DOK ECODR3 FL 04VRS FK01 EN P SIC_2_AE WMF Fig 9 12 Signal Control ...
Страница 348: ...11 18 Command Communications ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 418: ...13 4 Connectors ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 469: ...ECODRIVE03 FL 04VRS IDS Accessories 16 3 DOK ECODR3 FL 04VRS FK01 EN P IDS_mas_AE WMF Fig 16 5 IDS Dimensions ...
Страница 470: ...16 4 IDS Accessories ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 489: ......