6-44
Writing the User Program
ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
MOM - Torque Limitation
or
Continuous torque limit in %. (100% corresponds to motor current level at
standstill; Parameter CM02)
input range of 000%…500%
Warning: The Parameter A115 monitoring function remains active.
500% = torque limiting is turned off.
Bit: Torque limiting is only active when the selected bit is set to 1.
M0 – M5, M8, I0 -I4, Q0 - Q2
00.00.0 = torque limiting is always active
Maximum torque at positive stop in % (only valid with an active PFA/PFI
command)
Maximum torque during movement to positive stop in % (only valid with
an active PFA/PFI command)
Axis 1
This command is used to preselect the maximum torque values in % for
the drive unit.
Torque limiting remains in effect until the next MOM command is invoked
or as long as automatic mode is activated. When reactivating Automatic
Mode, the limit is set to 500 percent.
It is also possible to overwrite the torque limiting command while the drive
is running.
Note:
When the MOM command is used, error messages may be
generated if the torque limit is set too low ('F228 – Excessive
Deviation,' 'F878 – Velocity loop error’). To prevent these
error messages, position control circuit monitoring in
Parameter A115 can be deactivated.
Caution: If this monitoring function is disabled, a malfunction
may result in unmonitored acceleration of the drive unit!
Note:
The parameter CM01 "Bipolar Torque/Force Limit Value" limits
all previous settings via the MOM command. The smaller of
the two limit values in the MOM command and Parameter
CM01 is always used.
Please make appropriate data selections!
When using continuous torque limiting via the MOM
command, 100% corresponds with the motor current at
standstill. The peak current, which can reach four times the
continuous current level depending on the motor type, is also
limited to this value.
The program proceeds to the next instruction following the time period of
one cycle.
MOM 1 V600 V601 M2.02.3 V602
MOM 1 123 456 M2.02.3 100
Содержание Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS
Страница 18: ...XVI Table of Contents ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P ...
Страница 58: ...4 20 General Instructions for Start Up ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 187: ...ECODRIVE03 FL 04VRS Functions 8 41 DOK ECODR3 FL 04VRS FK01 EN P fp5007fj_AE WMF Fig 8 22 Control Loop ...
Страница 241: ...ECODRIVE03 FL 04VRS Parameters 9 29 DOK ECODR3 FL 04VRS FK01 EN P SIC_2_AE WMF Fig 9 12 Signal Control ...
Страница 348: ...11 18 Command Communications ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 418: ...13 4 Connectors ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 469: ...ECODRIVE03 FL 04VRS IDS Accessories 16 3 DOK ECODR3 FL 04VRS FK01 EN P IDS_mas_AE WMF Fig 16 5 IDS Dimensions ...
Страница 470: ...16 4 IDS Accessories ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Страница 489: ......