Operation using HART communicator
Azbil Corporation
7-36
Model MTG11A/18A, MTG11B/18B, MTG14C
7-3-2 : Output check
Analog output check with MGZ calibrator
This function is used for the loop check using MGZ calibrator. 0%, or 25% to 100% of
setting range can be selected for the analog output check with MGZ calibrator.
To output fixed value of analog current by using MGZ calibrator, proceed as follows.
1.
From online menu,
Select:
1. Device setup
2. Diag/Service
2. Loop test
1. Loop check mode
Figure 7-73
is then displayed
.
Figure 7-73
2.
Once the display as shown Figure 7-73
appears, make sure that the loop is
removed from the automatic control.
Then press “OK” to execute the output
check with MGZ calibrator.
Then Figure 7-74 is displayed.
Move the arrow key up or down and
select “1 Start” to execute the loop
check.
Figure 7-74
3.
During the loop check, Figure 7-75 is displayed. If the loop check is finished,
move the arrow key up or down and select “1 End” to select other analog
output value for the loop check. If you finish the loop check, move the arrow
key up or down and select “2 Abort” to abort. Then Figure 7-76 is displayed.
Figure 7-75
Figure 7-76
4.
Once the display as shown Figure 7-76 appears, press “OK” to abort. Then
Figure 7-77 is displayed. Press “OK” and then the screen returns to the loop
test menu as shown in Figure 7-78.
CM2-MTG300-2001.book 36 ページ 2015年9月29日 火曜日 午前10時14分
Содержание MagneW Neo PLUS
Страница 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Страница 92: ...MEMO CM2 MTG300 2001 book 38...
Страница 106: ...MEMO CM2 MTG300 2001 book 4...
Страница 266: ...MEMO CM2 MTG300 2001 book 82...
Страница 312: ...MEMO CM2 MTG300 2001 book 46...
Страница 336: ...MEMO CM2 MTG300 2001 book 22...
Страница 338: ...CM2 MTG300 2001 book 2...