Operation using the data setting device
Azbil Corporation
6-34
Model MTG11A/18A, MTG11B/18B, MTG14C
17
RAM FAULT
• A critical failure. Stop the electromagnetic
flow meter.
• The RAM of the converter is abnormal. Turn
OFF the power and then turn it ON again and
check the operation.
• If the same message still appears after taking
the action above, contact an Azbil Corp.
representative.
18
ROM FAULT
• A critical failure. Stop the electromagnetic
flow meter.
• The ROM of the converter is abnormal. Turn
OFF the power and then turn it ON again and
check the operation.
• If the same message still appears after taking
the action above, contact an Azbil Corp.
representative.
19
SFC FAULT
• An SFC error.
• Replace the SFC.
20
SPAN OVER ERROR
• As a result of setting the span, the maximum
measurable flow rate has exceeded 12 m/s.
• Check the span, diameter or type of the
detector.
21
>RANGE
• The calculation result of the SFC has exceeded
the display range.
• Restart the SFC.
• The SFC battery is running low.
22
:
• Charge the SFC.
• A minor fault.
23
#
• Press the
key and check the self-
diagnostics result of the SFC.
No.
Error message
Checkpoint and action
U
STAT
F/S DIR
CM2-MTG300-2001.book 34 ページ 2015年9月29日 火曜日 午前10時14分
Содержание MagneW Neo PLUS
Страница 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Страница 92: ...MEMO CM2 MTG300 2001 book 38...
Страница 106: ...MEMO CM2 MTG300 2001 book 4...
Страница 266: ...MEMO CM2 MTG300 2001 book 82...
Страница 312: ...MEMO CM2 MTG300 2001 book 46...
Страница 336: ...MEMO CM2 MTG300 2001 book 22...
Страница 338: ...CM2 MTG300 2001 book 2...