Operation using the data setting device
Azbil Corporation
6-78
Model MTG11A/18A, MTG11B/18B, MTG14C
Setting dropout [PULSE CONFIGURE] function
Dropout function is to fix the pulse output, which is caused by the output fluctuation
near 0% of flow rate and is unrelated to the flow rate. Use the following procedure to
set the dropout using SFC.
Range of the dropout setting is 0 to 10%.
Step
Key
Procedure
SFC screen
1
Confirm that the SFC is set to
“READY”.
If it is not, press the
key to
set it to “READY“.
2
or
Press the
key to access the
CONFIG functions. Press the
key or
key to display the
screen as shown on the right
3
or
Press the
key to access the
TOTALIZER functions. Press the
key or
key to display
the screen as shown on the right
4
or
Press the
key to enter into
PULSE setting function and press
the
key or
key to
display the screen as shown on the
right.
Displays the actual dropout setting.
CLR
( No )
CLR
( No )
SFCM00006009D
B
CONF
H
NEXT
L
PREV
B
CONF
H
NEXT
L
PREV
SFCM00006020D
SFCM00006136D
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
SFCM00006142D
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
SFCM00006153D
CM2-MTG300-2001.book 78 ページ 2015年9月29日 火曜日 午前10時14分
Содержание MagneW Neo PLUS
Страница 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Страница 92: ...MEMO CM2 MTG300 2001 book 38...
Страница 106: ...MEMO CM2 MTG300 2001 book 4...
Страница 266: ...MEMO CM2 MTG300 2001 book 82...
Страница 312: ...MEMO CM2 MTG300 2001 book 46...
Страница 336: ...MEMO CM2 MTG300 2001 book 22...
Страница 338: ...CM2 MTG300 2001 book 2...