Operation using the data setting device
Azbil Corporation
6-54
Model MTG11A/18A, MTG11B/18B, MTG14C
Setting high/low alarm values [ALARM CONFIG] function
Use the following procedure to set the high and low alarm values. High and low alarm
values can be used only when contact output is selected. (Refer to “Select pulse output
/ contact output [DIGITAL I/O] function” on page 6-60)
Setting range of the both high and low alarm values are 0 up to 115%. Set the values as
to be HI > LO.
Step
Key
Procedure
SFC screen
1
Confirm that the SFC is set to
“READY”.
If it is not, press the
key to set
it to “READY”
2
or
Press the
key to access the
CONFIG functions.
Press the
key or
key to
display the screen as shown on the
right.
3
or
Press the
key and press the
key or
key to display the
screen as shown on the right.
Actual high alarm value appears.
4
Press numeric keys and enter the
high alarm value to be set.
5
Press the
key.
The changed setting is saved to the
SFC.
CLR
( No )
CLR
( No )
SFCM00006009D
B
CONF
H
NEXT
L
PREV
B
CONF
H
NEXT
L
PREV
SFCM00006086D
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
ENTER
( Yes )
NON-VOL
H
NEXT
L
PREV
SFCM00006087D
SFCM00006088D
ENTER
( Yes )
NON-VOL
ENTER
( Yes )
NON-VOL
SFCM00006089D
CM2-MTG300-2001.book 54 ページ 2015年9月29日 火曜日 午前10時14分
Содержание MagneW Neo PLUS
Страница 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Страница 92: ...MEMO CM2 MTG300 2001 book 38...
Страница 106: ...MEMO CM2 MTG300 2001 book 4...
Страница 266: ...MEMO CM2 MTG300 2001 book 82...
Страница 312: ...MEMO CM2 MTG300 2001 book 46...
Страница 336: ...MEMO CM2 MTG300 2001 book 22...
Страница 338: ...CM2 MTG300 2001 book 2...