Operation using HART communicator
Azbil Corporation
7-30
Model MTG11A/18A, MTG11B/18B, MTG14C
Gain adjustment
To adjust gain, proceed as follows:
1.
From online menu,
Select:
1. Device setup
2. Diag/Service
3. Calibration
4. Gain trim
Figure 7-55 will then be displayed.
If the control system is not affected by
the forcible change of the current
signal, press F4 (OK). By pressing F3
(ABORT), the procedure is canceled.
Figure 7-55
2.
Figure 7-56 will then appears. Connect
the calibrator, and then press F4 (OK).
Figure 7-56
3.
Once the display as shown in Figure 7-
57 appears, move the arrow key up or
down to select a gain to adjust, and
then press F4 (ENTER). This time,
select 0 m/s.
Figure 7-57
4.
Figure 7-58 will then appear. Set the
connected calibrator value to 0.0 m/s
and then press F4 (OK).
Figure 7-58