Operation using HART communicator
Model MTG11A/18A, MTG11B/18B, MTG14C
7-37
Analog output check
To output fixed value of analog current, proceed as follows:
Figure 7-77
Figure 7-78
1.
From online menu,
Select:
1. Device setup
2. Diag/Service
2. Loop test
2. Out put check AO
Figure 7-79 will then be displayed.
If the control system is not affected by
the forcible change of the current
signal, press F4 (OK). By pressing F3
(ABORT), the procedure is canceled.
Figure 7-79
2.
Figure 7-80 will then appear. Choose
START to start fixed value of analog
current output, and then press F4
(ENTER)
Figure 7-80
3.
Note of caution will appear as shown
in Figure 7-81. To proceed, press F4
(OK).
Figure 7-81