Azbil Corporation
Electrical wiring
Model MTG11A/18A, MTG11B/18B, MTG14C
3-9
Wiring procedure
Carry out the wiring between the instrument and a power supply must be done
according to the following procedure.
*: The numerical value in parentheses is a reference value.
Step
Procedure
1
The terminal box cover is fixed by hexagon socket head setscrews (M3).
Loosen the setscrews with an Allen wrench (1.5).
2
Remove the terminal box cover by turning it counterclockwise with the
dedicated tool.
3
Remove the dust plug from the socket for an output signal line conduit.
4
Insert the cable into the conduit cable ground.
~Note •
Take care not to damage the cable sheath.
5
Referring to Figure 3-6, connect the cable to the output signal terminals
(IOUT+, -) of the terminal box.
~Note •
Pay attention to the polarity.
•
Tighten the terminal screws adequately. The
recommended tightening torque is 1.1 ft·lb (1.5 N·m)*.
6
Waterproof the conduit sufficiently to prevent ingression of rainwater, etc.
~Note •
We recommend using a silicon resin-based non-curing
sealant.
7
Attach the terminal box cover and tighten it adequately with the
dedicated tool. Then, fix the cover with the setscrews.
~Note •
Take care not injure your fingers on the cover edge or the
carrying thread.
CM2-MTG300-2001.book 9 ページ 2015年9月29日 火曜日 午前10時14分
Содержание MagneW Neo PLUS
Страница 16: ...List of Figures Tables CM2 MTG300 2001 book 4...
Страница 92: ...MEMO CM2 MTG300 2001 book 38...
Страница 106: ...MEMO CM2 MTG300 2001 book 4...
Страница 266: ...MEMO CM2 MTG300 2001 book 82...
Страница 312: ...MEMO CM2 MTG300 2001 book 46...
Страница 336: ...MEMO CM2 MTG300 2001 book 22...
Страница 338: ...CM2 MTG300 2001 book 2...