SmartPAC PRO Servo User Manual
1147100
Chapter 2
– Installation
55
Wiring Setup Mode Circuit
SmartPAC PRO Servo Setup mode allows you to disable green sensors and parts/batch counters,
using a remote switch. Typically, the Setup mode circuit is enabled when Inch mode is selected on
your main control. When you inch the press, SmartPAC PRO Servo will not stop the press when a
fault condition is detected. The Setup mode terminal can be wired to an extra contact on the Inch
switch of your main control, or you can use an external switch to activate the circuit. If you intend to
use the Setup mode circuit, plan how you will run your wiring for this connector now so you do not
have to disconnect conduit or rerun wires through conduit later.
For Setup mode, you must provide contact closure when the main control is in Inch mode. Connect a
wire from SmartPAC PRO Servo terminal block TB 5, terminal #252 (SETUP) to one side of a
normally open switch, Table 2-10, page 60, and Figure 3 at the end of the manual). Connect the other
side of the switch to GND (TB5, terminal #250). Refer to your electrical prints or the manual for your
control to plan your wiring.
Wiring a Remote Reset Switch (Optional)
Like the Setup mode terminal, the Remote Reset terminal can be wired to a normally open switch to
activate the circuit. Be sure to plan how you will run your wiring for this connector so that you do not
have to disconnect conduit or re-run wires through conduit later. Connect a wire from SmartPAC
PRO Servo TB5, terminal #249 (REM RES) to a normally open switch (see Table 2-10, page 60, and
Figure 3 at the end of the manual). Connect another wire from the switch to GND (TB5, terminal
#250). SmartPAC PRO Servo is reset with a momentary connection to ground.
Wiring a Sensor-Disabled Output (Optional)
You can wire a Sensor-disabled Output such as a warning light to a customer-supplied solid state
relay to warn personnel that the die protection capability, if installed, is disabled. Connect the positive
input wire from your 12Vdc solid-state relay to terminal #302 (Relay Pwr) on TB553 on the
DiProPAC board (see Figure 4 or 5 at the end of the manual). Connect the negative input wire from
the relay to terminal #306 (Aux 1) on TB553. You cannot use more than 8 mA for your relay.
Summary of Contents for SmartPAC PRO Servo
Page 2: ......
Page 4: ......
Page 14: ......
Page 16: ......
Page 18: ......
Page 26: ...1147100 SmartPAC PRO Servo User Manual 26 Chapter 1 Introduction ...
Page 70: ...1147100 SmartPAC PRO Servo User Manual 70 Chapter 3 Displays and Operating Modes ...
Page 158: ...1147100 SmartPAC PRO Servo User Manual 158 Chapter 5 Program Mode ...
Page 204: ......
Page 206: ......
Page 208: ......
Page 210: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......