SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
2014-MAY-02 REV. 0 PAGE 6-15
CHECKFIRE 210
Detection and Actuation System
TABLE 6-3: OPERATIONAL TEST (Continued)
Electric Manual Actuator (EMA) Test
CAUTION
If the system includes Pneumatic Manual Actuator(s), test
these components separately in accordance with the appro-
priate system manual (latest edition):
LT-A-101-10/20/30 Manual (Part No. 24327)
LT-A-101-50/125/250 Manual (Part No. 427865)
LVS Manual (Part No. 427109)
The actuators also have ring pins and red strike buttons.
Actuation can cause fire suppression system release.
1. Pull ring pin and strike red button to manually operate
EMA.
Note: There is no time delay upon manual activation.
2. Release Activated – The Red “PUSH to Activate / Alarm
When Lit” LED, Red Shutdown LED, Red Detection 1
(or Detection 2) LED and sounder are steady-on for 10
seconds.
3. Post Release Activated – The Red Detection 1 (or
Detection 2) LED, Red Shutdown LED, and sounder
pulse 1 x 10 seconds.
4. Confirm successful release signal (Pass) on RCT.
009290
POST RELEASE
ACTIVATED
CONTINUES UNTIL
MODULE IS RESET
RED LEDs AND
SOUNDER PULSE
1 X 10 SECONDS
009290
RELEASE
ACTIVATED
RED LEDs AND
SOUNDER REMAIN
STEADY-ON FOR 10
SECONDS
NOTE: DETECTION
2 LED WILL PULSE
WHEN EMA IS
INSTALLED ON
DETECTION
CIRCUIT #2
PULL RING PIN AND
STRIKE RED BUTTON
009240