SECTION 5 – INSTALLATION ANd prOgrAmmINg
2014-MAY-02 REV. 0 PAGE 5-33
TABLE 5-5: pErSONAL COmpUTEr (pC) OpTIONS (Continued)
CHECKFIRE 210
Detection and Actuation System
reading System Information
with proper communications established the software auto-
matically populates system information, including serial
numbers, firmware versions, and current programming.
At initial System startup, all programming options are
programmed to factory defaults.
Note: If display module is not connected to the ICM, the
display module information is shown as “No response.”
programming The System Clock
The internal real-time clock, default programmed to Green-
wich Mean Time (GMT), can be programmed to the date and
time on the PC (typically local time). In the Controller Date/
Time section click the Set Time button to synchronize the
ICM clock with the PC date and time. The system clock can
be updated multiple times as required.
Note: Programming the date/time does not affect the history
file.
009328
SERIAL NUMBER AND FIRMwARE VERSIONS
009329
SYNCHRONIZES ICM
CLOCK wITH PC CLOCK