SECTION 9 – TROUBLESHOOTING
2014-MAY-02 REV. 0 PAGE 9-3
CHECKFIRE 210
Detection and Actuation System
TABLE 9-2: RELEASE LED INDICATIONS
AMBER Release LED
Amber Release LED and Sounder pulsing 1 x 10 seconds
indicating Release Circuit fault.
• Check Release Circuit Cables for an open circuit or a
ground fault; replace cables as needed
• Check connections
• Indicates post release activated when combined with
Shutdown LED and/or other LEDs. Check for activated
or missing PAD(s); replace as needed following Section
8 – Recharge, Inspection, and Maintenance, page 8-1, for
Recharge instructions.
RED Shutdown LED
Red Shutdown LED, and Sounder pulsing 1 x 10 seconds
indicating Post Release Activated Mode/Release Circuit
Fault.
• Indicates Post Release Activated System release, proceed
to Section 8 – Recharge, Inspection, and Maintenance,
page 8-1, for Recharge instructions.
For more information see TABLE 9-7: Specific Circuit
Testing Procedures.
009290
RELEASE CIRCUIT
FAULT
AMBER LED AND
SOUNDER PULSE
1 X 10 SECONDS
009290
POST RELEASE
ACTIVATED MODE/
RELEASE CIRCUIT
FAULT
RED LED AND
SOUNDER PULSE
1 X 10 SECONDS