SECTION 9 – TROUBLESHOOTING
PAGE 9-4 REV. 0 2014-MAY-02
CHECKFIRE 210
Detection and Actuation System
TABLE 9-3: DETECTION LED INDICATIONS
AMBER Detection 1 and/or 2 LED
Applies to Detection Circuit #1 and/or #2.
Amber Detection Circuit #1 and/or #2 LED and Sounder
pulsing 1 x 10 seconds indicating Detection Circuit fault.
• Check connections on the indicated circuit(s)
• Check Detection Circuit Cables for an open circuit or a
ground fault; replace cables as needed
• Verify Linear Detector or Spot Thermal Detector continuity
or ground fault condition. Replace as needed
RED Detection 1 and/or 2 LED
Applies to either Detection Circuit #1 or #2.
Red Detection Circuit #1 and/or #2 LED and Sounder pulsing
1 x 1 seconds indicating Detection Circuit alarm condition.
• Investigate alarm condition in hazard area
• Check for damaged or activated detectors
• Check for damaged cables
• Check connections on the indicated circuit(s)
Red Detection Circuit #1 and/or #2 LED and Sounder pulsing
1 x 10 seconds indicating Detection Circuit alarm condi-
tion during Post Release Activated Mode. Refer to Section
8 – Recharge, Inspection, and Maintenance, page 8-1, for
Recharge instructions.
• Investigate alarm condition in hazard area
• Check for damaged or activated detectors
• Check for damaged cables
• Check connections on the indicated circuit(s)
For more information see TABLE 9-7: Specific Circuit
Testing Procedures.
009290
DETECTION CIRCUIT
FAULT
AMBER LED(
s) AND
SOUNDER PULSE
1 X 10 SECONDS
009290
DETECTION CIRCUIT
ALARM CONDITION
RED LED(s) AND
SOUNDER PULSE
1 X 1 SECONDS
009290
DETECTION CIRCUIT
ALARM CONDITION
- DURING
POST RELEASE
ACTIVATED MODE
RED LED(s) AND
SOUNDER PULSE
1 X 10 SECONDS