SECTION 1 – SYSTEM DESCRIPTION
2014-MAY-02 REV. 0 PAGE 1-1
SYSTEM DESCRIPTION
The CHECKFIRE 210 Detection and Actuation System is typi-
cally used with an ANSUL A-101 or LVS Vehicle Fire Suppres-
sion System for 24-hour protection of equipment. The system
is designed for vehicles/equipment in extreme environmental
and physical conditions.
Industries Where Vehicles Use CHECKFIRE 210 Systems:
• Forestry
• Public utilities
• Agriculture
• Land fills
• Construction
• Waste disposal
• Public transportation
• Mining
The automatic detection and actuation system provides two
monitored input circuits and one monitored output circuit to
activate an ANSUL fire suppression system. On detecting a
fire condition, the system activates the release circuit resulting
in the discharge of an expellant gas cartridge initiating fire
suppression system operation. Optional pneumatic actuation is
available.
CHECKFIRE 210 System Features
• Supervised power, detection, release, and communication
circuits
• System may be powered by internal battery and/or external
power
• Two time delays programmable to 0, 5, 10 or 15 seconds
• “DELAY/Reset/Silence” button
• “PUSH To Activate / Alarm When Lit” electric manual activa
-
tion button and LED
• Color-coded “Plug and Play” connections
• 85 dB internal sounder
• Dust and water tight (IP67 rated)
• Manual programming button
• Computer programmable via mini USB port
• Two analog detection circuits, detection circuit #2 may be
programmed for pressure switch feedback
• Detection circuits are programmable for independent detec
-
tion and release, cross-zone detection and release or detec-
tion only
• Auxiliary Power output available when external power is
connected
• Two internal programmable SPDT Form “C” relays (5A @
30 VDC automotive)
• Isolate switch
• Downloadable 4000+ Event History Log
CHECKFIRE 210 System Specifications
SYSTEM POWER (24 HOUR OPERATION)
Supervised internal 3.6 VDC power source
Connection for 12/24 VDC external power source when
required
SYSTEM CURRENT DRAW*
Nominal 6 mA @ 10.2 VDC
• Maximum Alarm/Fault 80 mA @ 10.2 VDC
Nominal 6 mA @ 28.0 VDC
• Maximum Alarm/Fault 35 mA @ 28.0 VDC
*Does not include AUX OUTPUT load of up to 1.5 A
OPERATING TEMPERATURE LIMITS
– 40 °F to 185 °F (– 40 °C to 85 °C)
APPROVALS
FM Approved and CE Marked
CHECKFIRE 210 System Connectivity
The CHECKFIRE 210 Display Module (see Figure 1-1)
communicates with the CHECKFIRE 210 Interface Control
Module (ICM) through the Display Cable. The black color-
coded connector securely attaches to the ICM receptacle using
threaded circular connectors.
DISPLAY
CABLE
BLACK
CONNECTOR
FIGURE 1-1
CHECKFIRE 210 DISPLAY MODULE
009272
CHECKFIRE 210
Detection and Actuation System