SECTION 6 – OPERATIONAL TEST AND PLACE IN SERVICE
2014-MAY-02 REV. 0 PAGE 6-7
CHECKFIRE 210
Detection and Actuation System
TABLE 6-3: OPERATIONAL TEST (Continued)
Detection Circuit #1 (and #2) - Supervision Test
Confirm DCT is in place of the EOL Device on Detection
Circuit #1. Set DCT switch to “Fault” position. The CHECK-
FIRE 210 Display Module indicates the following:
1. Amber Detection 1 LED and sounder pulse 1 x 10
seconds.
2. If fault relay is programmed, confirm activation of
connected devices.
3. Push the “DELAY/Reset/Silence” button to test sounder
silence. Sounder silences and LED continues.
4. Reset the DCT to the “Normal” position.
5. CHECKFIRE 210 Display Module returns to normal
status; Power LED is GREEN steady-on.
Release Circuit - Supervision Test
Remove RCT from the Release Circuit. The CHECKFIRE
210 Display Module indicates the following.
1. Amber Release LED and sounder pulse 1 x 10 seconds.
2. Push the “DELAY/Reset/Silence” button to test sounder
silence. Sounder silences and LED continues.
3. Reconnect RCT to release circuit.
4. CHECKFIRE 210 Display Module returns to normal
status; Power LED is GREEN steady-on.
009290
RECONNECT RCT
MODULE
RETURNS TO
NORMAL STATUS
POWER LED IS
GREEN STEADY-ON
009290
RESET DCT TO
NORMAL
MODULE
RETURNS TO
NORMAL STATUS
POWER LED IS
GREEN STEADY-ON
009290
DETECTION 1
FAULT INDICATION
(DCT = FAULT)
AMBER LED AND
SOUNDER PULSE
1 X 10 SECONDS
PUSH BUTTON
SOUNDER STOPS
009290
RELEASE
FAULT INDICATION
(RCT REMOVED)
AMBER LED AND
SOUNDER PULSE
1 X 10 SECONDS
PUSH BUTTON
SOUNDER STOPS